Contact Closure Interface (CCI)
The Contact Closure Interface (CCI) enables external dry-contact devices, such as switches, relays, and timers, to trigger configured lighting actions in the Signify Interact for Intelligent Buildings system.
Configure Contact Closure Interface (CCI)
Prerequisite
Before commissioning CCI, verify the following:
-
The target group must support Light behavior V2, and group/network version must be 6.0 or later.
To ensure group/network version is 6.0 or later, navigate to Group → Controls → Behavior settings in Signify Interact Builder mobile app and check the Add state button is available.
If the Add state button is not available, the group does not supports Light behavior V2.
-
If the group is not Light behavior V2-compatible, complete the applicable migration procedure before adding CCI. For migration instructions, see Migration scenarios for Light behavior V2.
-
All devices in the target group must run firmware version 8.x.x or later.
Updating firmware alone does not migrate an existing group to Light behavior V2. -
You can create and configure a CCI even when no lights are assigned to the group. However, to realize all CCI features it is recommended to have few lights in the group.
-
While commissioning, ensure you are in line-of-sight with CCI and within the BLE range.
Follow the steps to configure a CCI.
-
Navigate to the appropriate Group, then tap Controls.
-
Tap Input/output devices.
-
On the Input/output devices screen, tap Add input/output device.
-
Tap Contact Closure Input Module.
Result: The Installation Instructions page appears, displaying the CCI wiring diagram and the predefined Open and Closed behaviors for Inputs 1 through 4. These input behavior assignments are fixed and cannot be modified.
Before commissioning, read the following expected CCI behavior to ensure correct installation and operation.
-
All CCI inputs are treated with the same priority. If more than one input is activated at the same time, the associated actions are executed sequentially. The order in which the actions are performed is not defined and may vary.
-
For reliable operation, configure and use only one CCI input (Input 1, 2, 3, or 4) for a specific use case. Unused inputs are not expected to trigger any action.
-
Commands received from different CCI devices, including Network-level and Group/Zone-level CCIs, have equal priority. As a result, a Network-level OFF command is not designed to override or remain dominant over subsequent Group/Zone-level commands from other CCI devices.
-
The system does not retain the state of CCI inputs. Therefore, input states are evaluated only when actions are triggered.
Connect each CCI input using its corresponding Input (+) and Common (–) terminals. Do not interchange or rewire the Input (+) and Common (–) connections. Incorrect wiring can result in unexpected or unintended device behavior. -
-
Tap Next.
-
The Add CCI screen appears. When mains powered is ON, LED light flashes for 10 second to configure CCI from the mobile app.
If CCI is not added within 10 seconds, and to add press the Reset button on CCI for more than 5 seconds and the LED light will start blinking.
-
Once CCI is detected, enter or modify the device name, and then tap Save.
-
On the Configure CCI screen, select either the Group or Network radio button, depending on whether the CCI should control devices within a specific group or across the network, and then tap Save.
Result: The CCI is added and displayed on the Input/output devices screen. If Network is selected, (network control) is displayed next to the assigned group name, indicating that the CCI is configured for network-level control.
-
Deploy the changes. For more information, see Deploy settings.
Result: The CCI configuration is deployed for the selected Group or Network.
-
To view the CCI configuration, navigate to Controls → Input/output devices.
-
Swipe left on the required CCI, and then tap the 3-dot ellipsis icon.
-
Optional: Tap Blink Module LED.
Result: The CCI LED blinks for 5 seconds to help you identify the device when multiple CCI devices are configured in the group.
-
Tap Show wiring instructions.
Result: The Installation instructions screen appears, displaying the CCI wiring diagram and the predefined Open and Closed behaviors for Inputs 1 through 4.
|
To reset CCI device, press the Reset button on CCI for 10 seconds and the LED light starts blinking. When the LED light remains ON, the reset is complete.
|
Delete Contact Closure Interface (CCI)
Follow the steps to remove a Contact Closure Interface (CCI).
|
Before deleting a CCI from a group or network, ensure that the CCI is not actively applying an override. If you delete the CCI while an override is active, the associated lights in the group or network will remain in the applied override state. If the associated lights remain in the override state after a CCI deletion, perform one of the following actions to restore normal lighting operation:
|
-
Navigate to Controls → Input/output devices.
-
Swipe left on the required CCI.
-
Tap the Delete icon.
OR
Tap the 3-dot ellipsis icon, and then tap Delete.
-
Confirm the deletion.
Result: The CCI is removed from the Input/output devices list.